Place of Origin: | CHINA |
---|---|
Brand Name: | DONGJIAXIN |
Certification: | QS |
Model Number: | N-YJV |
Minimum Order Quantity: | Negotiable |
Price: | Negotiable |
Packaging Details: | Steel wooden drum, Coil In Foil / Drum |
Delivery Time: | 7-15 working days |
Payment Terms: | L/C, T/T, Western Union, MoneyGram |
Supply Ability: | 100KM/WEEK |
Model Name: | N-YJV | Conductor Type:: | Class 2 |
---|---|---|---|
Temperature Rating:: | -25C Up To +90℃ | Jacket:: | PVC |
Size:: | 1.5~630mm² | Nos.of Core:: | 2~5 |
Insulation :: | XLPE | Voltage Suitable:: | 0.6/1kV |
Highlight: | 1kV pvc power cable,cu xlpe pvc power cable |
▼0.6/1 kV copper conductor YJV 3x185+1x90 cu xlpe pvc power cable
▼Application
1kV for Fixed installations such as distribution networks or industrial installations.
▼Constraction
Core Conductor | annealed copper (stranded core) |
Popular sizes | 2~5 core x1.5~630mm² |
Insulation | XLPE |
Jacket | PVC |
Voltage suitable | 0.6/1kV |
Standards Certificates | IEC 60502-1 |
▼Advantage
It has excellent thermal-mechanical properties, excellent electrical properties and chemical corrosion resistance, and also has the advantages of simple structure, light weight, and no drop limit for laying.
1. Insulation performance:
XLPE maintains the original good insulation properties of PE, and the insulation resistance is further increased. The dielectric loss tangent value is very small, and it is not greatly affected by temperature.
2. Mechanical properties:
Due to the establishment of new chemical bonds between macromolecules, the hardness, stiffness, wear resistance and impact resistance of XLPE have been improved, thereby making up for the shortcomings of PE being vulnerable to environmental stress and cracking.
▼Technical parameters
2 Core&3 Core
Cross section of conductor(mm²) | Conductor structure | Insulation Thickness(mm) | Copper sheath thickness(mm) | Approx.cable diameter(mm) | Max resistance of conductor at 20℃ (Ω/km) |
3×6 | 1 | 0.7 | 1.8 | 14.7 | 3.08 |
3×10 | 7 | 0.7 | 1.8 | 16.9 | 1.83 |
3×16 | 7 | 0.7 | 1.8 | 19.1 | 1.15 |
3×25 | 7 | 0.9 | 1.8 | 22.5 | 0.727 |
3×35 | 7 | 0.9 | 1.8 | 24.7 | 0.524 |
3×50 | 10 | 1.0 | 1.8 | 27.8 | 0.387 |
3×70 | 14 | 1.1 | 1.9 | 31.6 | 0.268 |
3×95 | 19 | 1.1 | 2.0 | 38.0 | 0.193 |
3×120 | 24 | 1.2 | 2.1 | 42.0 | 0.153 |
3×150 | 30 | 1.4 | 2.3 | 45.8 | 0.124 |
3×185 | 37 | 1.6 | 2.4 | 50.9 | 0.0991 |
3×240 | 48 | 1.7 | 2.6 | 57.7 | 0.0754 |
3×300 | 61 | 1.8 | 2.7 | 63.0 | 0.0601 |
▼ Testing process
▼ Shipping:
For big orders, we will ship the goods by air or by sea.
ss section of conductor(mm²) | Conductor structure(mm) | Insulation thickness(mm) | Approx. cable diameter(mm) | Max resistance of conductor at 20℃ (Ω/km) |
0.5 | 16/0.19 | 0.6 | 2.1±0.1 | 39.0 |
0.75 | 24/0.19 | 0.6 | 2.3±0.1 | 26.0 |
1 | 32/0.19 | 0.6 | 2.5±0.1 | 19.5 |